Accumulate technical expertise

Coagulant Selection and Dosage Calculation for High-Efficiency Flocculation Sedimentation Tanks

2026-05-03Author:Technical Department

1. Classification and Characteristics of Coagulants

1. Inorganic coagulants
• Polyaluminum Chloride (PAC): Wide pH adaptability (5-9), suitable for various wastewater types
• Polyferric Sulfate (PFS): Heavy flocs, fast settling; ideal for low-temperature, low-turbidity water.
• Ferric chloride: Excellent coagulation performance, but highly corrosive.

2. Organic polymeric flocculants
• Polyacrylamide (PAM): Cationic, Anionic, and Nonionic
• Features: Low dosage (1-5mg/L), large floc size, high strength

II. Principles of Reagent Selection

1. Select based on wastewater type
• Domestic sewage: PAC + PAM (cationic)
• Oily wastewater: PFS + PAM (cationic)
• Dyeing and printing wastewater: PAC + PAM (anionic)
• Pulp and paper wastewater: PFS + cationic PAM

2. Select based on water quality characteristics
• pH 5-7: Prefer PFS
• pH 7-9: Prefer PAC
• Low temperature (<10°C): PFS outperforms PAC

3. Dosage Calculation

1. Expert Estimation Method
• Domestic sewage: PAC 20-50 mg/L, PAM 1-3mg/L
• Industrial Wastewater: PAC/PFS 50-200 mg/L, PAM 2-5mg/L

2. Beaker Test Method (Recommended)
Determine the optimal dosage through bench-scale testing for accurate, reliable results that serve as the basis for engineering design.

IV. Factors Affecting Coagulation Efficiency

• pH: Optimal range for PAC is 6.5-7.5, and for PFS is 5-7
• Water temperature: Optimal 20-30°C; increase dosage at lower temperatures
• Mixing conditions: high-speed mixing at 150-300 rpm, low-speed mixing at 20-60 rpm
• Dosing order: Inorganic first, then organic, with a 1-3 minute interval.

V. Conclusion

Coagulation-sedimentation is the most widely used process in wastewater treatment. Selecting the right chemicals and controlling their dosage are critical to ensuring treatment effectiveness. Shandong Zhongnan Environmental Protection Equipment Co., Ltd. provides professional technical support and tailored solutions for our clients.

About the Data and Author

Compiled by the Technical Department of Shandong Zhongnan Environmental Protection Equipment Co., Ltd. This content is derived from parameter records and common issues identified during equipment design, full-unit manufacturing, and on-site commissioning. It should not be used to replace field testing based on a single project conclusion.

Refer to standards including GB 18918 "Discharge Standard of Pollutants for Municipal Wastewater Treatment Plants," GB 8978 "Comprehensive Discharge Standard of Water Pollutants," GB/T 31962 "Water Quality Standard for Sewage Discharged into Urban Sewers," and HJ 2010 "Technical Specification for Membrane Bioreactor Wastewater Treatment Engineering." For specific projects, applicable standards shall be determined based on environmental impact assessment approval, discharge permits, and contractual agreements.

If you have questions about the parameters or selection methods in this article, pleaseContact UsAccompany with water quality test reports and operating conditions; we will provide explanations based on the specific project requirements.

Lü ICP Bei 2026002929 Hao-2|Lu Gong An Wang Bei 37070202000697